402

EMCP 4.4 Master Control Panel

The EMCP 4.4 Master Control Panel is a wall mounted system that monitors and controls up to eight engine generators for operation in parallel with or without a single utility source.

  • Specifications

  • Standard/Optional Equipment

  • Catalog

Configuration

Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.

Modes of Operation

Emergency standby, island, utility paralleling

Application

LV and MV (208V - 38 kV)

ANSI Protective Devices

15/25, 27/59, 81 O/U, 32, 40, 50, 51

ANSI Protective Devices

15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Certifications

IBC, CBC, UBC & OSHPD Certified

Control Panel Enclosure

NEMA 1 wall-mounted construction

Operating Temperature

0°C to 50°C

Storage Temperature

-20°C to +60°C

Low Voltage Standards

NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70

Medium Voltage Standards

NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

Emergency Transfer Load Manager Optional Equipment

Utility Monitoring and Circuit Breaker Control I/O provided in XLM version of Master Control Panel provided in XLM version of Master Control Panel

Related Products - Attachments

Diesel Generator Sets - C9, C13, C15, C18, C27, C32, 3500, C175

Configuration

Wall mounted supervisory control system provides centralized monitoring and control of up to eight generators equipped with EMCP4.4 paralleling control panels

Application

LV and MV (208V - 15 kV) 50/60Hz

Operating Temperature

0-50 C

Medium Voltage Standards

UL 508A

Emergency Transfer Load Manager Standard Equipment

Data Table Interface

19" Color Touchscreen

ALL

Configuration

Wall mounted supervisory control system provides centralized monitoring and control of up to eight generators equipped with EMCP4.4 paralleling control panels

Application

LV and MV (208V - 15 kV) 50/60Hz

Operating Temperature

0-50 C

Medium Voltage Standards

UL 508A

Emergency Transfer Load Manager Standard Equipment

Data Table Interface

19" Color Touchscreen

Optional Equipment

Emergency Transfer Load Manager Optional Equipment

Utility Monitoring and Circuit Breaker Control I/O provided in XLM version of Master Control Panel provided in XLM version of Master Control Panel

Related Products - Attachments

Diesel Generator Sets - C9, C13, C15, C18, C27, C32, 3500, C175

    Send an Enquiry