Specifications
-
Standard/Optional Equipment
- Catalog
Configuration
Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application
LV and MV (208V-27kV)
ANSI Protective Devices
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)
ANSI Protective Devices
15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)
Certifications
UL / cUL 508A
Control Panel Enclosure
NEMA 12
Operating Temperature
0°C to 55°C
Storage Temperature
-20°C to 60°C
Generator Control Panel (for 3-10 gensets)
With breaker position indications and circuit breaker control switch
Utility Control Panel (for utility paralleling and control)
With utility close lockout switch, breaker position indications, and circuit breaker control switch
Supplemental Hardware 25 Device
Provides additional discrete synchronization protection
Data Table Interface
Accommodates interface with a building management system
Generator Demand Priority Control
An automatic priority sequencing function to modulate the number of gensets online to control load percentages per machine, assist with fuel efficiency, and maintain adequate reserve capacity
Instant Auto Selector Switch
Allows user to return sysem to automatic in the event of a touchscreen failure
ALL
Instant Auto Selector Switch
Allows user to return sysem to automatic in the event of a touchscreen failure
Optional Equipment
Generator Control Panel (for 3-10 gensets)
With breaker position indications and circuit breaker control switch
Utility Control Panel (for utility paralleling and control)
With utility close lockout switch, breaker position indications, and circuit breaker control switch
Supplemental Hardware 25 Device
Provides additional discrete synchronization protection
Data Table Interface
Accommodates interface with a building management system
Generator Demand Priority Control
An automatic priority sequencing function to modulate the number of gensets online to control load percentages per machine, assist with fuel efficiency, and maintain adequate reserve capacity