402

3516B Generator Set

The 3516B generator set has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance that matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.

  • Specifications

  • Standard/Optional Equipment

  • Catalog

Standby Rating

2250 kVA

Prime Power Rating

2000 kVA

Emissions/Fuel Strategy

Low fuel, Low Emissions

Voltage

380 to 11000 Volts

Frequency

50 Hz

Speed

1500 rpm

Duty Cycle

Standby, Mission Critical, Prime, Continuous

Maximum Rating

2250 kVA

Minimum Rating

1750 kVA

Engine Model

3516B TA, V-16, 4-Stroke Water-Cooled Diesel

Bore

6.69in

Stroke

7.48in

Displacement

4210.64in

Compression Ratio

14.0:1 Std

Aspiration

TA

Fuel System

Electronic unit injection

Governor Type

Adem™3

Length - Maximum

234.5in

Width - Maximum

90in

Height - Maximum

98.2in

Dry Weight - Genset (maximum)

34460lb

Control System

EMCP 4.3, EMCP 4.4

Controller: [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4

Local annunciator module: [ ] NFPA 110 [ ] Custom

Air Inlet System

Dual element air cleaner

Single element filter

Engine Options

Air cleaner: [ ] Single element air cleaners [ ] Dual element air cleaners [ ] Heavy duty air cleaners

Battery charger: [ ] 10A [ ] 20A [ ] 35A

Starting aids: [ ] 220V 50 Hz Jacket water heater

Muffler: [ ] Industrial Grade

Starting motors: [ ] Standard [ ] Heavy duty

Batteries: [ ] Standard (1400 CCA) [ ] Heavy Duty (2800 CCA)

Cooling System

Standard ambient radiators

Coolant

Optional installed radiators

Optional installed ATAAC radiators

Water level switch gauges

Standard ambient ATAAC radiators

Crankcase System

Ventilation system

No explosion relief valves

Explosion relief valves

Exhaust System

Y Adapters

Flanges

Tier 4 clean emission MOD Kits

Clean emission parts

Flange and exhaust expanders

Flexible fittings

Exhaust offset

Mufflers

Tier 4 dosing cabinet

Tier 4 clean emissions module

Elbows

Alternators

Temperature rise (over 40°C ambient): [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C

Power Termination

Power termination: [ ] Busbar [ ] Circuit breaker

Circuit breaker trip unit: [ ] LSI [ ] LSIG [ ] LSIG-P

Circuit breaker rating: [ ] 2000A [ ] 2500A [ ] 3200A [ ] 4000A

Fuel System

Fuel priming pumps (Tier 4) - Manual or electric

Primary fuel filter

Extended Service Contract (ESC)

Extended Service Contract (ESC): [ ] 2 Year [ ] 3 Year [ ] 5 Year

General

Special paint (Colors other than Caterpillar yellow or high performance paints)

US aid emblem

Generators and Attachments

Generator conversion

Space heater

Alternator air cleaner

Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame

Differential current transformers (DCT)

Differential current transformers (DCT) 8.7 kV and 15 kV classes

Thermostat for space heater

Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames

Instrumentation

Pyrometer and thermocouples

Lubrication System

Oil level regulator

Prelube pumps

Lube oil in standard sump

Mounting System

Puck style low efficiency isolators

IBC vibration isolators

Spring type vibration isolators

Power Connections

Neutral ground connections

Center post busbars

Right side power connections

Left side power connections

2700 Frame, four lead, four terminal

Ground cables between generator and terminal box

Low voltage Circuit breakers

Rear power connections

Special Tests / Reports

Torsional vibration analysis reports

Generator set fuel consumption test

PGS Test report @ 1.0 power factor

Fuel consumption test

Standard engine test charge

IBC Certification

OSHPD Certification

Canadian Standards Association certification

PGS Test report @ 0.8 power factor

Generator test report

Starting and Charging

10, 20, 35 and 50 Amp Battery chargers

Air starting motors

Air pressure regulator

Electric starting motors

Starter cover

Jacket water heaters

Engine barring device

24 Volt battery set - Dry

Extended Service Coverage

Platinum, Gold and Silver coverage

Air Inlet System

Air cleaner; single element canister type

Control Panels

Auto/start/stop control

Engine cool-down timer

Environmental sealed front face

Emergency stop pushbutton

Text alarm/event descriptions

24 Volt DC operation

Controls:

Generator mounted - Rear facing

IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min / max exciter.

Limiter and exciter diode monitor

Generator set packages include Caterpillar's voltage regulator

EMCP 4.2B

Speed adjust

Alarm acknowledge

Engine cycle crank

Load histogram feature

Lamp test

Digital indication for:

Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy

RPM

PLC functionality

Operating hours

Oil pressure (psi, kPa or bar)

Coolant temperature

DC volts

Power factor (per phase & average)

Volts (L-L & L-N)

kW (per phase, average & percent)

Amps (per phase & average)

Frequency (Hz)

kVA (per phase, average & percent)

kVAr (per phase, average & percent)

Low oil pressure - High coolant temperature

kVAr-hr (total)

High coolant temperature

Warning/shutdown with common LED indication of shutdowns for:

kW-hr (total)

Overspeed

Low coolant temperature

Failure to start (overcrank)

Emergency stop

Over/under voltage (27 / 59)

Generator phase sequence

Low coolant level

Programmable protective relaying functions:

6 Customer programmable digital inputs

Over/under frequency (81 o/u)

Reverse reactive power (kVAr) (32RV)

Serial annunciator module data link

Reverse power (kW) (32)

Number of I/O varies on options selected

Overcurrent (50 / 51)

Cat connect

4 Programmable relay outputs (Form A)

Communications:

Customer data link (Modbus RTU)

1 Programmable digital outputs

1 Programmable relay outputs (Form C)

Accessory module data link

3 Analog inputs

Cooling System

Certified standard PGS provided

Exhaust System

Dry exhaust manifold

Flanged faced outlet(s)

Fuel System

Fuel cooler; not included with packages without radiator

Secondary fuel filters

Fuel priming pump

Flexible fuel lines - shipped loose

General

Right hand servicing

SAE standard rotation

Flywheel and flywheel housing - SAE No. 00

Caterpillar yellow with high gloss black rails and radiator

Generator and Attachments

Busbar connections, right side extension box, bottom cable entry

High voltage:

NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)

Form wound

Internal excitation (IE)

NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)

3 Phase brushless, Salient pole

Medium voltage:

NEMA standard hole pattern

Permanent magnet excitation (PMG)

Permanent magnet excitation (PMG)

Winding temperature detectors

Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)

Winding temperature detectors

Low voltage:

Form wound

6 Leads
 

Random wound

Anti-condensation space heater

Winding temperature detectors

Busbar connections, top center mounted, top cable entry

NEMA standard hole pattern

Governing System

ADEM A3

Literature

Parts book

Lubrication System

Integral lube oil cool

Lubricating oil

Oil filter, filler and dipstick

Gear type lube oil pump

Oil drain lines and valve

Fumes disposal

Mounting System

Rails - Engine/generator/radiator mounting

Rubber anti-vibration mounts - shipped loose

Anti-vibration mounts (shipped loose)

Starting System

24 Volt electric starting motor

45 Amp Charging alternator

Battery disconnect switch

Battery and battery rack w/cables

ALL

Air Inlet System

Air cleaner; single element canister type

Control Panels

Auto/start/stop control

Engine cool-down timer

Environmental sealed front face

Emergency stop pushbutton

Text alarm/event descriptions

24 Volt DC operation

Controls:

Generator mounted - Rear facing

IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min / max exciter.

Limiter and exciter diode monitor

Generator set packages include Caterpillar's voltage regulator

EMCP 4.2B

Speed adjust

Alarm acknowledge

Engine cycle crank

Load histogram feature

Lamp test

Digital indication for:

Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy

RPM

PLC functionality

Operating hours

Oil pressure (psi, kPa or bar)

Coolant temperature

DC volts

Power factor (per phase & average)

Volts (L-L & L-N)

kW (per phase, average & percent)

Amps (per phase & average)

Frequency (Hz)

kVA (per phase, average & percent)

kVAr (per phase, average & percent)

Low oil pressure - High coolant temperature

kVAr-hr (total)

High coolant temperature

Warning/shutdown with common LED indication of shutdowns for:

kW-hr (total)

Overspeed

Low coolant temperature

Failure to start (overcrank)

Emergency stop

Over/under voltage (27 / 59)

Generator phase sequence

Low coolant level

Programmable protective relaying functions:

6 Customer programmable digital inputs

Over/under frequency (81 o/u)

Reverse reactive power (kVAr) (32RV)

Serial annunciator module data link

Reverse power (kW) (32)

Number of I/O varies on options selected

Overcurrent (50 / 51)

Cat connect

4 Programmable relay outputs (Form A)

Communications:

Customer data link (Modbus RTU)

1 Programmable digital outputs

1 Programmable relay outputs (Form C)

Accessory module data link

3 Analog inputs

Cooling System

Certified standard PGS provided

Exhaust System

Dry exhaust manifold

Flanged faced outlet(s)

Fuel System

Fuel cooler; not included with packages without radiator

Secondary fuel filters

Fuel priming pump

Flexible fuel lines - shipped loose

General

Right hand servicing

SAE standard rotation

Flywheel and flywheel housing - SAE No. 00

Caterpillar yellow with high gloss black rails and radiator

Generator and Attachments

Busbar connections, right side extension box, bottom cable entry

High voltage:

NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)

Form wound

Internal excitation (IE)

NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)

3 Phase brushless, Salient pole

Medium voltage:

NEMA standard hole pattern

Permanent magnet excitation (PMG)

Permanent magnet excitation (PMG)

Winding temperature detectors

Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)

Winding temperature detectors

Low voltage:

Form wound

6 Leads<br />  

Random wound

Anti-condensation space heater

Winding temperature detectors

Busbar connections, top center mounted, top cable entry

NEMA standard hole pattern

Governing System

ADEM A3

Literature

Parts book

Lubrication System

Integral lube oil cool

Lubricating oil

Oil filter, filler and dipstick

Gear type lube oil pump

Oil drain lines and valve

Fumes disposal

Mounting System

Rails - Engine/generator/radiator mounting

Rubber anti-vibration mounts - shipped loose

Anti-vibration mounts (shipped loose)

Starting System

24 Volt electric starting motor

45 Amp Charging alternator

Battery disconnect switch

Battery and battery rack w/cables

Optional Equipment

Control System

EMCP 4.3, EMCP 4.4

Controller: [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4

Local annunciator module: [ ] NFPA 110 [ ] Custom

Air Inlet System

Dual element air cleaner

Single element filter

Engine Options

Air cleaner: [ ] Single element air cleaners [ ] Dual element air cleaners [ ] Heavy duty air cleaners

Battery charger: [ ] 10A [ ] 20A [ ] 35A

Starting aids: [ ] 220V 50 Hz Jacket water heater

Muffler: [ ] Industrial Grade

Starting motors: [ ] Standard [ ] Heavy duty

Batteries: [ ] Standard (1400 CCA) [ ] Heavy Duty (2800 CCA)

Cooling System

Standard ambient radiators

Coolant

Optional installed radiators

Optional installed ATAAC radiators

Water level switch gauges

Standard ambient ATAAC radiators

Crankcase System

Ventilation system

No explosion relief valves

Explosion relief valves

Exhaust System

Y Adapters

Flanges

Tier 4 clean emission MOD Kits

Clean emission parts

Flange and exhaust expanders

Flexible fittings

Exhaust offset

Mufflers

Tier 4 dosing cabinet

Tier 4 clean emissions module

Elbows

Alternators

Temperature rise (over 40°C ambient): [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C

Power Termination

Power termination: [ ] Busbar [ ] Circuit breaker

Circuit breaker trip unit: [ ] LSI [ ] LSIG [ ] LSIG-P

Circuit breaker rating: [ ] 2000A [ ] 2500A [ ] 3200A [ ] 4000A

Fuel System

Fuel priming pumps (Tier 4) - Manual or electric

Primary fuel filter

Extended Service Contract (ESC)

Extended Service Contract (ESC): [ ] 2 Year [ ] 3 Year [ ] 5 Year

General

Special paint (Colors other than Caterpillar yellow or high performance paints)

US aid emblem

Generators and Attachments

Generator conversion

Space heater

Alternator air cleaner

Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame

Differential current transformers (DCT)

Differential current transformers (DCT) 8.7 kV and 15 kV classes

Thermostat for space heater

Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames

Instrumentation

Pyrometer and thermocouples

Lubrication System

Oil level regulator

Prelube pumps

Lube oil in standard sump

Mounting System

Puck style low efficiency isolators

IBC vibration isolators

Spring type vibration isolators

Power Connections

Neutral ground connections

Center post busbars

Right side power connections

Left side power connections

2700 Frame, four lead, four terminal

Ground cables between generator and terminal box

Low voltage Circuit breakers

Rear power connections

Special Tests / Reports

Torsional vibration analysis reports

Generator set fuel consumption test

PGS Test report @ 1.0 power factor

Fuel consumption test

Standard engine test charge

IBC Certification

OSHPD Certification

Canadian Standards Association certification

PGS Test report @ 0.8 power factor

Generator test report

Starting and Charging

10, 20, 35 and 50 Amp Battery chargers

Air starting motors

Air pressure regulator

Electric starting motors

Starter cover

Jacket water heaters

Engine barring device

24 Volt battery set - Dry

Extended Service Coverage

Platinum, Gold and Silver coverage

    Send an Enquiry