Specifications
-
Standard/Optional Equipment
- Catalog
Standby Rating
2500/2250/2000 ekW
Prime Power Rating
2250/2045/1825 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 2
Voltage
380 to 13800 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous
Maximum Rating
2500 ekW
Minimum Rating
1650 ekW
Engine Model
3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
Bore
6.69in
Stroke
7.48in
Stroke - HD
8.46in
Displacement
4764.73in
Compression Ratio
14.7:1
Aspiration
TA
Fuel System
Electronic unit injection
Governor Type
Adem™3
Length - Minimum
266.2in
Length - Maximum
276.3in
Width - Minimum
92.1in
Width - Maximum
92.1in
Height - Minimum
118in
Height - Maximum
118in
Dry Weight - Genset (minimum)
35880lb
Dry Weight - Genset (maximum)
38780lb
Control System
EMCP 4.4
Exhaust
Exhaust mufflers
Air Inlet System
Single element filter
Dual element air cleaner
Generator
Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
Oversize and premium generators
Anti-condensation heater
Cooling System
Coolant
Standard ambient ATAAC radiators
Optional installed radiators
Optional installed ATAAC radiators
Standard ambient radiators
Water level switch gauges
Power Termination
Circuit breakers, UL listed
Circuit breakers, IEC compliant
Crankcase System
Explosion relief valves
Ventilation system
No explosion relief valves
Control Panels
Load share module
Digital I/O module
Generator temperature monitoring & protection
Remote monitoring software
Mounting
Rubber anti-vibration mounts
IBC isolators
Exhaust System
Y Adapters
Flexible fittings
Exhaust offset
Tier 4 clean emissions module
Elbows
Flange and exhaust expanders
Tier 4 clean emission MOD Kits
Tier 4 dosing cabinet
Flanges
Mufflers
Clean emission parts
Starting/Charging
Oversize batteries
Battery chargers
Charging alternator
Air starting motor with control and silencer
Heavy duty starting system
Fuel System
Primary fuel filter
General
The following options are based on regional and product configuration:
UL 2200 package
CSA Certification
EEC Declaration of Conformity
Special paint (Colors other than Caterpillar yellow or high performance paints)
Integral & sub-base fuel tanks
US aid emblem
Enclosures: Sound attenuated, weather protective
Automatic transfer switches (ATS)
Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
EU Certificate of Conformance (CE)
Integral & sub-base UL listed dual wall fuel tanks
Generators and Attachments
High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
Thermostat for space heater
Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
Differential current transformers (DCT) 8.7 kV and 15 kV classes
Generator conversion
Space heater kit
Alternator air cleaner
Instrumentation
Pyrometer and thermocouples
Lubrication System
Oil level regulator
Lube oil in standard sump
Prelube pumps
Mounting System
Puck style low efficiency isolators
Spring type vibration isolators
IBC vibration isolators
Power Connections
Ground cables between generator and terminal box
Neutral ground connections
Left side power connections
Center post busbars
Right side power connections
2700 Frame, four lead, four terminal
Rear power connections
Low voltage Circuit breakers
Special Tests / Reports
IBC Certification
Fuel consumption test
Generator test report
PGS Test report @ 1.0 power factor
Torsional vibration analysis reports
OSHPD Certification
Generator set fuel consumption test
PGS Test report @ 0.8 power factor
Standard engine test charge
Canadian Standards Association certification
Starting and Charging
Air pressure regulator
Starter cover
Air starting motors
10, 20, 35 and 50 Amp Battery chargers
Electric starting motors
Jacket water heaters
24 Volt battery set - Dry
Engine barring device
Extended Service Coverage
Platinum, Gold and Silver coverage
Air Inlet System
Air cleaner; single element canister type
Cooling
Package mounted radiator
Exhaust
Exhaust flange outlet
Control Panels
Communications:
Reverse reactive power (kVAr) (32RV)
Customer data link (Modbus RTU)
Generator mounted - rear facing
1 Programmable digital outputs
Auto/start/stop control -
Serial annunciator module data link
Engine cool-down timer
24 Volt DC operation
Controls:
Generator set packages include Caterpillar's voltage regulator (IVR). IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min / max exciter. Limiter and exciter diode monitor
Alarm acknowledge
Cat connect
Engine cycle crank
Text alarm/event descriptions
Overcurrent (50 / 51)
Accessory module data link
Cat ECS 100
1 Programmable relay outputs (Form C)
Emergency stop pushbutton
Speed adjust
4 Programmable relay outputs (Form A)
Number of I/O varies on options selected
6 Customer programmable digital inputs
Environmental sealed front face
Load histogram feature
Lamp test
PLC functionality
Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
Digital indication for:
Operating hours
RPM
DC volts
Frequency (Hz)
Coolant temperature
Volts (L-L & L-N)
Oil pressure (psi, kPa or bar)
Amps (per phase & average)
kVAr (per phase, average & percent)
kVA (per phase, average & percent)
kW (per phase, average & percent)
Power factor (per phase & average)
kW-hr (total)
kVAr-hr (total)
High coolant temperature
Overspeed
Failure to start (overcrank)
Warning/shutdown with common LED indication of shutdowns for:
Emergency stop
Low oil pressure
Low coolant level
Low coolant temperature
Programmable protective relaying functions:
Over/under frequency (81 o/u)
Generator phase sequence
Over/under voltage (27 / 59)
Reverse power (kW) (32)
Fuel
Primary fuel filter with integral water separator
Generator
Matched to the performance and output characteristics of Cat engines
IP23 Protection
Power Termination
Busbar
Control Panel
Cat ECS Genset controller
Cooling System
Certified standard PGS provided
Exhaust System
Flanged faced outlet(s)
Dry exhaust manifold
Fuel System
Flexible fuel lines - shipped loose
Fuel cooler; not included with packages without radiator
Secondary fuel filters
Fuel priming pump
General
Caterpillar yellow with high gloss black rails and radiator
Right hand servicing
Flywheel and flywheel housing - SAE No. 00
Paint - Caterpillar yellow except rails and radiators gloss black
SAE standard rotation
Generator and Attachments
Busbar connections, top center mounted, top cable entry
Class H temperature rise at 40C ambient (125C prime / 150C standby)
Low voltage:
NEMA standard hole pattern
Medium voltage:
Anti-condensation space heater
6 Lead
Random wound
Form wound
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)
Permanent magnet excitation (PMG)
Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
Internal excitation (IE)
3 Phase brushless, Salient pole
High voltage:
Winding temperature detectors
Busbar connections, right side extension box, bottom cable entry
Governing System
ADEM A3
Literature
Parts book
Lubrication System
Lubricating oil
Fumes disposal
Integral lube oil cool
Oil drain lines and valve
Oil filter, filler and dipstick
Gear type lube oil pump
Mounting System
Anti-vibration mounts (shipped loose)
Rubber anti-vibration mounts - shipped loose
Rails - engine/generator/radiator mounting
Starting System
Battery disconnect switch
45 Amp Charging alternator
24 Volt electric starting motor
Battery and battery rack w/cables
ALL
Air Inlet System
Air cleaner; single element canister type
Cooling
Package mounted radiator
Exhaust
Exhaust flange outlet
Control Panels
Communications:
Reverse reactive power (kVAr) (32RV)
Customer data link (Modbus RTU)
Generator mounted - rear facing
1 Programmable digital outputs
Auto/start/stop control -
Serial annunciator module data link
Engine cool-down timer
24 Volt DC operation
Controls:
Generator set packages include Caterpillar's voltage regulator (IVR). IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min / max exciter. Limiter and exciter diode monitor
Alarm acknowledge
Cat connect
Engine cycle crank
Text alarm/event descriptions
Overcurrent (50 / 51)
Accessory module data link
Cat ECS 100
1 Programmable relay outputs (Form C)
Emergency stop pushbutton
Speed adjust
4 Programmable relay outputs (Form A)
Number of I/O varies on options selected
6 Customer programmable digital inputs
Environmental sealed front face
Load histogram feature
Lamp test
PLC functionality
Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
Digital indication for:
Operating hours
RPM
DC volts
Frequency (Hz)
Coolant temperature
Volts (L-L & L-N)
Oil pressure (psi, kPa or bar)
Amps (per phase & average)
kVAr (per phase, average & percent)
kVA (per phase, average & percent)
kW (per phase, average & percent)
Power factor (per phase & average)
kW-hr (total)
kVAr-hr (total)
High coolant temperature
Overspeed
Failure to start (overcrank)
Warning/shutdown with common LED indication of shutdowns for:
Emergency stop
Low oil pressure
Low coolant level
Low coolant temperature
Programmable protective relaying functions:
Over/under frequency (81 o/u)
Generator phase sequence
Over/under voltage (27 / 59)
Reverse power (kW) (32)
Fuel
Primary fuel filter with integral water separator
Generator
Matched to the performance and output characteristics of Cat engines
IP23 Protection
Power Termination
Busbar
Control Panel
Cat ECS Genset controller
Cooling System
Certified standard PGS provided
Exhaust System
Flanged faced outlet(s)
Dry exhaust manifold
Fuel System
Flexible fuel lines - shipped loose
Fuel cooler; not included with packages without radiator
Secondary fuel filters
Fuel priming pump
General
Caterpillar yellow with high gloss black rails and radiator
Right hand servicing
Flywheel and flywheel housing - SAE No. 00
Paint - Caterpillar yellow except rails and radiators gloss black
SAE standard rotation
Generator and Attachments
Busbar connections, top center mounted, top cable entry
Class H temperature rise at 40C ambient (125C prime / 150C standby)
Low voltage:
NEMA standard hole pattern
Medium voltage:
Anti-condensation space heater
6 Lead
Random wound
Form wound
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)
Permanent magnet excitation (PMG)
Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
Internal excitation (IE)
3 Phase brushless, Salient pole
High voltage:
Winding temperature detectors
Busbar connections, right side extension box, bottom cable entry
Governing System
ADEM A3
Literature
Parts book
Lubrication System
Lubricating oil
Fumes disposal
Integral lube oil cool
Oil drain lines and valve
Oil filter, filler and dipstick
Gear type lube oil pump
Mounting System
Anti-vibration mounts (shipped loose)
Rubber anti-vibration mounts - shipped loose
Rails - engine/generator/radiator mounting
Starting System
Battery disconnect switch
45 Amp Charging alternator
24 Volt electric starting motor
Battery and battery rack w/cables
Optional Equipment
Control System
EMCP 4.4
Exhaust
Exhaust mufflers <!--(except Tier 4)-->
Air Inlet System
Single element filter
Dual element air cleaner
Generator
Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
Oversize and premium generators
Anti-condensation heater
Cooling System
Coolant
Standard ambient ATAAC radiators
Optional installed radiators
Optional installed ATAAC radiators
Standard ambient radiators
Water level switch gauges
Power Termination
Circuit breakers, UL listed
Circuit breakers, IEC compliant
Crankcase System
Explosion relief valves
Ventilation system
No explosion relief valves
Control Panels
Load share module
Digital I/O module
Generator temperature monitoring & protection
Remote monitoring software
Mounting
Rubber anti-vibration mounts
IBC isolators
Exhaust System
Y Adapters
Flexible fittings
Exhaust offset
Tier 4 clean emissions module
Elbows
Flange and exhaust expanders
Tier 4 clean emission MOD Kits
Tier 4 dosing cabinet
Flanges
Mufflers
Clean emission parts
Starting/Charging
Oversize batteries
Battery chargers
Charging alternator
Air starting motor with control and silencer
Heavy duty starting system
Fuel System
Primary fuel filter
General
The following options are based on regional and product configuration:
UL 2200 package
CSA Certification
EEC Declaration of Conformity
Special paint (Colors other than Caterpillar yellow or high performance paints)
Integral & sub-base fuel tanks
US aid emblem
Enclosures: Sound attenuated, weather protective
Automatic transfer switches (ATS)
Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
EU Certificate of Conformance (CE)
Integral & sub-base UL listed dual wall fuel tanks
Generators and Attachments
High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
Thermostat for space heater
Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
Differential current transformers (DCT) 8.7 kV and 15 kV classes
Generator conversion
Space heater kit
Alternator air cleaner
Instrumentation
Pyrometer and thermocouples
Lubrication System
Oil level regulator
Lube oil in standard sump
Prelube pumps
Mounting System
Puck style low efficiency isolators
Spring type vibration isolators
IBC vibration isolators
Power Connections
Ground cables between generator and terminal box
Neutral ground connections
Left side power connections
Center post busbars
Right side power connections
2700 Frame, four lead, four terminal
Rear power connections
Low voltage Circuit breakers
Special Tests / Reports
IBC Certification
Fuel consumption test
Generator test report
PGS Test report @ 1.0 power factor
Torsional vibration analysis reports
OSHPD Certification
Generator set fuel consumption test
PGS Test report @ 0.8 power factor
Standard engine test charge
Canadian Standards Association certification
Starting and Charging
Air pressure regulator
Starter cover
Air starting motors
10, 20, 35 and 50 Amp Battery chargers
Electric starting motors
Jacket water heaters
24 Volt battery set - Dry
Engine barring device
Extended Service Coverage
Platinum, Gold and Silver coverage