402

XQP310 EU Stage V

  • Specifications

  • Standard/Optional Equipment

  • Catalog

Rating Prime

310 kVA

Frequency

50/60 Hz

Voltage

220 - 480 V

Fuel/Emissions Strategy

EU Stage V

Engine

Cat C9.3

Fuel

Diesel

Width

60in

Height

90in

Length

161in

Weight - With Lube Oil and Coolant

9046lb

100% Load 50 Hz

17.7gal/hr

100% Load 60 Hz

20.4gal/hr

75% Load 50 Hz

13.2gal/hr

75% Load 60 Hz

14.9gal/hr

Control Panel

ComAp InteliGen NTC, Deep Sea 8620, DEIF AGC-4

Syncronising capabilities

Distribution

CE socket box with integrated MCB & RCBO protection

Fuel Option Pack

Inboard mounted 3-way valve for external fuel connection, electronic fuel gauge and Bund Level Sender

Drains option Pack

Oil and coolant drains piped to base frame

Cat® C9.3B Diesel Engine

Twin Turbocharged, air-to-air aftercooler

Electronic ECM controlled

After Treatment

Engine Mounted Clean Emissions Module (CEM)

Diesel Emissions Fluid (DEF)

Alternator

LC5114N Frame

Coastal insulation protection

Control Panel

XQCP set mounted digital controller

Air Filter

High efficiency two stage air cleaner, with dust cup andservice indicator

Cat Connect remote monitoring

Provides package monitoring and management

Cooling System

Package mounted radiator with vertical air discharge. Filled from factory

High ambient performance

Charging / Starting System

24V heavy duty charging alternator with integral regulator

Fuel System

12hour dual wall fuel tank with internal fuel fill

Engine mounted primary and secondary fuel filter

Distribution

Separate robust steel enclosures for control & distribution sections

4 pole, 630A main circuit breaker

Enclosure

Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance

Sealed quarter-turn compression latches with key orpadlock capabilities

Lube Oil

On engine primary and secondary oil filters. Filled from factory

General

Factory tested and inspected

Full manufacturer's warranty

ALL

Cat® C9.3B Diesel Engine

Twin Turbocharged, air-to-air aftercooler

Electronic ECM controlled

After Treatment

Engine Mounted Clean Emissions Module (CEM)

Diesel Emissions Fluid (DEF)

Alternator

LC5114N Frame

Coastal insulation protection

Control Panel

XQCP set mounted digital controller

Air Filter

High efficiency two stage air cleaner, with dust cup andservice indicator

Cat Connect remote monitoring

Provides package monitoring and management

Cooling System

Package mounted radiator with vertical air discharge. Filled from factory

High ambient performance

Charging / Starting System

24V heavy duty charging alternator with integral regulator

Fuel System

12hour dual wall fuel tank with internal fuel fill

Engine mounted primary and secondary fuel filter

Distribution

Separate robust steel enclosures for control & distribution sections

4 pole, 630A main circuit breaker

Enclosure

Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance

Sealed quarter-turn compression latches with key orpadlock capabilities

Lube Oil

On engine primary and secondary oil filters. Filled from factory

General

Factory tested and inspected

Full manufacturer's warranty

Optional Equipment

Control Panel

ComAp InteliGen NTC, Deep Sea 8620, DEIF AGC-4

Syncronising capabilities

Distribution

CE socket box with integrated MCB & RCBO protection

Fuel Option Pack

Inboard mounted 3-way valve for external fuel connection, electronic fuel gauge and Bund Level Sender

Drains option Pack

Oil and coolant drains piped to base frame

    Send an Enquiry