Specifications
-
Standard/Optional Equipment
- Catalog
Rating Range
200 to 5000A
Transfer Type
Open Transition
Switch Type
Power Breaker
Control Power
Fixed Mount 200-3200A 2, 3, or 4 Pole
Drawout 200-5000A 2-, 3-, 4-pole
System Voltage Application
120 - 600 Vac, 50/60 Hz
Time Withstand
85,000 for 30 cycles
Withstand
100,000 amps withstand/closing/ interrupting at 600 Vac
Applicable Testing
CSA C22.2 No. 178 certified
IBC 2006, CBC 2007 and OSHPD
Available Options
Load sequencing contacts
Multi-meter options available
Controller availability: ATC-100, ATC-300+,and ATC-800
2- or 4-position test switch
Remote communications
Integral overcurrent protection
Field selectable, multi ratio, control voltage transformer 50/60 Hz
Suitable for service entrance
Space heaters
Open or closed transition
Surge suppression
Selectable automatic or non-automatic operation
Optional Delayed Transition includes:
Time delay neutral
In-phase transition
Pre-transfer signal with 1 N.O. and 1 N.C. contacts
Controls and Wiring
All controls relays and industrial grade relays are totally encapsulated to minimize exposure to dust and dirt. Lugs are 90º rated and all control wire is #16 AWG, type XLPE with a 125º temperature rating.
Enclosure
Durable powder-coated steel NEMA 1, 3R or 12 enclosures with three door hinges to ensure proper support of the door and door mounted devices. The hinges have removable hinge pins to facilitate door removal for easy wall mounting or service and are supplied with pad-lockable latches.
ALL
Controls and Wiring
All controls relays and industrial grade relays are totally encapsulated to minimize exposure to dust and dirt. Lugs are 90º rated and all control wire is #16 AWG, type XLPE with a 125º temperature rating.
Enclosure
Durable powder-coated steel NEMA 1, 3R or 12 enclosures with three door hinges to ensure proper support of the door and door mounted devices. The hinges have removable hinge pins to facilitate door removal for easy wall mounting or service and are supplied with pad-lockable latches.
Optional Equipment
Available Options
Load sequencing contacts
Multi-meter options available
Controller availability: ATC-100, ATC-300+,and ATC-800
2- or 4-position test switch
Remote communications
Integral overcurrent protection
Field selectable, multi ratio, control voltage transformer 50/60 Hz
Suitable for service entrance
Space heaters
Open or closed transition
Surge suppression
Selectable automatic or non-automatic operation
Optional Delayed Transition includes:
Time delay neutral
In-phase transition
Pre-transfer signal with 1 N.O. and 1 N.C. contacts