Specifications
-
Standard/Optional Equipment
- Catalog
Rating Prime
1100 kVA
Frequency
50/60 Hz
Voltage
127 - 480 V
Engine
Cat C32
Fuel
Diesel
Width
96in
Height
102in
Length
240in
Weight - With Lube Oil and Coolant
32053lb
100% Load 50Hz
57.6gal/hr
100% Load 60Hz
67gal/hr
75% Load 50Hz
43.2gal/hr
75% Load 60Hz
50gal/hr
50% Load 50Hz
30.6gal/hr
50% Load 60Hz
133.6l/hr
Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz)
84 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz)
85 dB(A)
CAT C32 Diesel Engine
Turbocharged
Generator
E3875L4 Frame
Air Filter
Cyclonic/paper with dust cup and service indicator
Cat Connect remote monitoring
Provides package monitoring and management
Cooling System
Package mounted radiator with vertical air discharge. Filled from factory
Charging / Starting System
24V heavy duty starting motor and charging alternator c/w battery isolator
Fuel System
Fuel tank with 6 way directional valve for external supply
Control Panel
Digital EMCP4.4 set mounted controller
Distribution
Single, robust enclosure for controls and distribution c/w 4 pole circuit breaker and safety cut off
Structure
Heavy Duty steel base frame with integral fuel tank. Fork lift pockets. Dragging bars. Lifting frame and 4 point lift. base frame is wider than enclosure to protect generator set during transportation.
Enclosure
Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance
Exhaust
Integrated spark arresting silencer
Lube Oil
On engine primary and secondary oil filters. Filled from factory
General
Factory tested and inspected
ALL
CAT C32 Diesel Engine
Turbocharged
Generator
E3875L4 Frame
Air Filter
Cyclonic/paper with dust cup and service indicator
Cat Connect remote monitoring
Provides package monitoring and management
Cooling System
Package mounted radiator with vertical air discharge. Filled from factory
Charging / Starting System
24V heavy duty starting motor and charging alternator c/w battery isolator
Fuel System
Fuel tank with 6 way directional valve for external supply
Control Panel
Digital EMCP4.4 set mounted controller
Distribution
Single, robust enclosure for controls and distribution c/w 4 pole circuit breaker and safety cut off
Structure
Heavy Duty steel base frame with integral fuel tank. Fork lift pockets. Dragging bars. Lifting frame and 4 point lift. base frame is wider than enclosure to protect generator set during transportation.
Enclosure
Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance
Exhaust
Integrated spark arresting silencer
Lube Oil
On engine primary and secondary oil filters. Filled from factory
General
Factory tested and inspected