Specifications
-
Standard/Optional Equipment
- Catalog
Rating Prime
500 kVA
Frequency
50/60 Hz
Voltage
127 - 480 V
Engine
Cat C15
Fuel
Diesel
Width
77in
Height
90in
Length
200.9in
Weight - With Lube Oil and Coolant
13176lb
100% Load 50Hz
29.1gal/hr
100% Load 60Hz
32gal/hr
75% Load 50Hz
23gal/hr
75% Load 60Hz
26.3gal/hr
50% Load 50Hz
16.4gal/hr
50% Load 60Hz
18.3gal/hr
100% Load 50Hz
29gal/hr
100% Load 60Hz
28.3gal/hr
75% Load 50Hz
20.1gal/hr
75% Load 60Hz
22gal/hr
50% Load 50Hz
14.3gal/hr
50% Load 60Hz
15.7gal/hr
Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz)
77.5 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz)
79.8 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz)
80.1 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz)
80 dB(A)
CAT C15 Diesel Engine
Turbocharged
Generator
LC6114F Frame
Air Filter
Cyclonic/paper with dust cup and service indicator
Cat Connect remote monitoring
Provides package monitoring and management
Cooling System
Package mounted radiator with vertical air discharge. Filled from factory
Charging / Starting System
24V heavy duty starting motor and charging alternator c/w battery isolator
Fuel System
Dual wall fuel tank with 3 way directional valve for external supply
Control Panel
Digital EMCP4.2B set mounted controller
Distribution
Single, robust enclosure for controls and distribution c/w 4 pole circuit breaker and safety cut off
Structure
Heavy Duty steel base frame with integral fuel tank. Fork lift pockets. Dragging bars. Lifting frame and 4 point lift. base frame is wider than enclosure to protect generator set during transportation.
Enclosure
Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance
Exhaust
Integrated spark arresting silencer
Lube Oil
On engine primary and secondary oil filters. Filled from factory
General
Factory tested and inspected
ALL
CAT C15 Diesel Engine
Turbocharged
Generator
LC6114F Frame
Air Filter
Cyclonic/paper with dust cup and service indicator
Cat Connect remote monitoring
Provides package monitoring and management
Cooling System
Package mounted radiator with vertical air discharge. Filled from factory
Charging / Starting System
24V heavy duty starting motor and charging alternator c/w battery isolator
Fuel System
Dual wall fuel tank with 3 way directional valve for external supply
Control Panel
Digital EMCP4.2B set mounted controller
Distribution
Single, robust enclosure for controls and distribution c/w 4 pole circuit breaker and safety cut off
Structure
Heavy Duty steel base frame with integral fuel tank. Fork lift pockets. Dragging bars. Lifting frame and 4 point lift. base frame is wider than enclosure to protect generator set during transportation.
Enclosure
Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance
Exhaust
Integrated spark arresting silencer
Lube Oil
On engine primary and secondary oil filters. Filled from factory
General
Factory tested and inspected