Specifications
-
Standard/Optional Equipment
- Catalog
Standby Rating
1500 ekW
Emissions/Fuel Strategy
Low BSFC
Voltage
400 to 415 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical
Maximum Rating
1500 ekW
Minimum Rating
1500 ekW
Mission Critical
1500 ekW
Engine Model
C32B TA, V12, 4-Stroke Diesel
Bore
5.7in
Stroke
6.4in
Displacement
1959in³
Compression Ratio
14:1
Aspiration
TA
Fuel System
EUI
Governor Type
ADEM™ A5
Length - Minimum
185.43in
Length - Maximum
185.43in
Width - Minimum
89.72in
Width - Maximum
89.72in
Height - Minimum
100.43in
Height - Maximum
105.71in
Dry Weight - Genset (minimum)
18832lb
Dry Weight - Genset (maximum)
20155lb
Starting
Oversize Batteries and Heavy Duty Electric Starter
Air Cleaner
Dual Element
Control Panel
GCCP 1.4
Cooling System
High Ambient Radiator
Attachments
Anti-condensation Heater
Mufflers
15 dBA Industrial Grade
Battery Chargers
20A
10A
Air Cleaner
Single Element
Starting
Standard Batteries and Electric Starter
Cooling System
Standard Radiator:
Alternator
380 V
480 V
Alternator Temperature Rise
80�C
105�C
125�C
150�C
Excitation
PM
IE
Control Panel
GCCP 1.3
Connectivity
Cat� Product Link� PL444 cellular
ALL
Air Cleaner
Single Element
Starting
Standard Batteries and Electric Starter
Cooling System
Standard Radiator:
Alternator
380 V
480 V
Alternator Temperature Rise
80�C
105�C
125�C
150�C
Excitation
PM
IE
Control Panel
GCCP 1.3
Connectivity
Cat� Product Link� PL444 cellular
Optional Equipment
Starting
Oversize Batteries and Heavy Duty Electric Starter
Air Cleaner
Dual Element
Control Panel
GCCP 1.4
Cooling System
High Ambient Radiator
Attachments
Anti-condensation Heater
Mufflers
15 dBA Industrial Grade
Battery Chargers
20A
10A