Specifications
-
Standard/Optional Equipment
- Catalog
Prime Power Rating
2275/2000 kVA
Continuous Rating
2000/1750 kVA
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
380 to 11000 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Prime, Continuous
Maximum Rating
2275 kVA
Minimum Rating
1750 kVA
Engine Model
3516B TA, V-16, 4-Stroke Water-Cooled Diesel
Bore
6.69in
Stroke
7.48in
Stroke - HD
8.46in
Displacement
4210.64in
Displacement - HD
4764.73in³
Compression Ratio
14.0:1 Std 15.5:1 HD
Aspiration
TA
Fuel System
Electronic unit injection
Governor Type
Adem™4
Length - Minimum
268.3in
Length - Maximum
276.1in
Width - Minimum
90.1in
Width - Maximum
90.1in
Height - Minimum
94.1in
Height - Maximum
94.1in
Dry Weight - Genset (minimum)
33300lb
Dry Weight - Genset (maximum)
36280lb
Exhaust
Exhaust mufflers
Air Inlet System
Dual element air cleaner
Standard ambient radiators
Single element filter
Standard ambient ATAAC radiators
Optional radiator arrangements
Generator
Permanent magnet excitation (PMG)
Oversize and premium generators
Internal excitation (IE)
Anti-condensation heater
Control Panels
Load share module
Empty upper box
Generator main terminal box
Annunciator - remote
EMCP 4.4
Digital I/O module
Cable Shroud
Remote monitoring software
Vandal proof panel cover
Side extension box
Generator temperature monitoring & protection
Annunciator - local
Cooling System
Water level switch gauges
Coolant
Mounting
IBC isolators
Spring type vibration isolators
Crankcase Systems
No explosion relief valves
Explosion relief valves
Crankcase ventilation systems
Crankcase protection groups:
Exhaust System
Tier 4 dosing cabinet
Y Adapters
Flanges
Flange and exhaust expanders
Elbows>
Mufflers
Tier 4 lean emissions moDual
Clean emission parts
Flexible fittings
Tier 4 clean emission MOD kits
Exhaust offset
Starting/Charging
Charging alternator
Battery chargers
Oversize batteries
Heavy duty starting system
Jacket water heater
Air starting motor with control and silencer
Extended Service Coverage
Platinum, Silver and Gold coverage
General
The following options are based on regional and product configuration:
UL 2200 package
EEC Declaration of Conformity
CSA Certification
Enclosures: Sound attenuated, weather protective
EU Certificate of Conformance (CE)
Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
Integral & sub-base UL listed dual wall fuel tanks
Automatic transfer switches (ATS)
Integral & sub-base fuel tanks
Fuel System
Gas fuel filter
Primary fuel filter
Fuel priming pumps (Tier 4)
Generators and Attachments
1600 Frame - 380, 400, 415 Volts, 3 Phase 1500 rpm ,FW, PM, No. of leads = 6, Pitch = .6667
Hi voltage optional attachments
Differential current transformers
1600 Frame - 380, 400, 415 Volts, 3 Phase 1500 rpm, RW, PM, No. of leads = 6, Pitch = .6667
Generators high voltage
Space heater kit
Generator conversions
1600 Frame - 380, 400, 415 Volts, 3 Phase 1500 rpm, RW, IE, No. of leads = 6, Pitch = .6667
2700 Frame - 6300, 6600, 6900 Volts, 3 Phase 1500 rpm, FW, PM, No. of leads = 6, Pitch = .6667
3000 Frame - 10000, 10500, 11000 Volts, 3 Phase 1500 rpm, FW, PM, No. of leads = 6, Pitch = .6667
1800 Frame
Alternator air cleaner
Instrumentation
Pyrometer and termocouples
Lube System
Prelube pump groups
Oil level regulator
Lube oil in standard sump
Mounting System
IBC vibration isolators
Puck style low efficiency isolators
Spring type vibration isolators
Power Connections
Cable entry - right side
Cable entry - rear
Grounding groups
left side power connections
Neutral ground connections
Center post busbars
Right side power connections
Cable entry - left side
Rear power connections
Power Termination
Circuit breakers - LV packages
Circuit breakers, UL listed
2000, 2500, 3200 Amp, 3 Pole, IEC rated Circuit breakers
Circuit breakers, IEC compliant
2000, 2500, 3200 Amp, 4 Pole, IEC rated Circuit breakers
1600, 2000, 2500, 3000 and 4000 Amp, 3 Pole, UL-100% rated Circuit breakers
Special Tests / Reports
Standard engine test
Torsional vibration analysis
Fuel consumption test
PGS Test report @ 1.0 power factor
OSPD Certification
PGS Test report @ 0.8 power factor
Generator set report
Starting / Charging
Engine barring device
Electric starting motors
Jacket water heaters
Starter cover
Batteries, racks and cables
Air pressure regulator
10, 20, 35 Amp Battery chargers
50 Amp NFPA battery charger
Air starting motors
Air Inlet System
Air cleaner, single element canister type
Control System
Low oil pressure
Over/under frequency (81 o/u)
Alarm acknowledge
Oil pressure (psi, kPa or bar)
Reverse reactive power (kVAr) (32RV)
3 Analog inputs
Programmable protective relaying functions:
4 Programmable relay outputs (Form A)
Overspeed
Reverse power (kW) (32)
Customer data link (Modbus RTU)
Text alarm/event descriptions
Low coolant temperature
Number of I/O varies on options selected
Emergency stop
Operating hours
Limiter and exciter diode monitor
Environmental sealed front face
kW (per phase, average & percent)
Digital indication for:
Auto/start/stop control
Cat connect
Low coolant level
Controls:
Serial annunciator module data link
Regulator (IVR) - IVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter
RPM
Volts (L-L & L-N), frequency (Hz)
Coolant temperature
1 Programmable digital outputs
Speed adjust
Engine cycle crank
Over/under voltage (27/59)
kW-hr (total)
6 Customer programmable digital inputs
Generator phase sequence
1 Programmable relay outputs (Form C)
PLC functionality
kVAr-hr (total)
DC volts
Engine cool-down timer
24 Volt DC operation
Generator mounted - rear facing
High coolant temperature
Amps (per phase & average)
Load histogram feature
Emergency stop pushbutton
Warning/shutdown with common LED indication of shutdowns for:
kVAr (per phase, average & percent)
Customizable screens
True RMS AC metering, 3-phase, +/-2% accuracy
Overcurrent (50/51)
Communications:
kVA (per phase, average & percent)
Power factor (per phase & average)
Failure to start (overcrank)
Accessory module data link
Lamp test
Generator set packages include Caterpillars voltage regulator
Exhaust
Exhaust flange outlet
Fuel
Primary fuel filter with integral water separator
Generator
IP23 Protection
Power Termination
Busbar
Control Panel
Cat ECS Genset controller
Cooling System
Package mounted radiator
Exhaust System
Dry exhaust manifold
Flanged faced outlet(s)
Fuel System
Fuel priming pump
Fuel cooler; not included with packages without radiator
Flexible fuel lines - shipped loose
Secondary fuel filters
General
SAE standard rotation
Paint - Caterpillar yellow except rails and radiators gloss black
RH service
Flywheel and Flywheel housing-SAE No. 00
Generators and Attachments
Matched to the performance and output characteristics of Cat engines
Random wound
Busbar connections, right side extension box, bottom cable entry - 60 Hz models: NEMA standard hole pattern
Permanent magnet excitation (PMG)
LV
HV:
MV:
6 Lead
Winding temperature detectors
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby) - 60 Hz models: NEMA standard hole pattern
Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)
3 Phase brushless, Salient pole
Anti-condensation space heater
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)
Form wound
Governing System
ADEM A3
Lube System
Gear type lube oil pump
Oil filter, filler and dipstick
Oil drain lines and valve
Integral lube Oil cooler
Lubricating oil
Fumes disposal
Mounting System
Rails - Engine/generator/radiator mounting
Rubber anti-vibration mounts - shipped loose
Anti-vibration mounts (shipped loose)
Starting System
45 Amp Charging alternator
24 Volt electric starting motor
Battery disconnect switch
Battery and battery rack w/cables
ALL
Air Inlet System
Air cleaner, single element canister type
Control System
Low oil pressure
Over/under frequency (81 o/u)
Alarm acknowledge
Oil pressure (psi, kPa or bar)
Reverse reactive power (kVAr) (32RV)
3 Analog inputs
Programmable protective relaying functions:
4 Programmable relay outputs (Form A)
Overspeed
Reverse power (kW) (32)
Customer data link (Modbus RTU)
Text alarm/event descriptions
Low coolant temperature
Number of I/O varies on options selected
Emergency stop
Operating hours
Limiter and exciter diode monitor
Environmental sealed front face
kW (per phase, average & percent)
Digital indication for:
Auto/start/stop control
Cat connect
Low coolant level
Controls:
Serial annunciator module data link
Regulator (IVR) - IVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter
RPM
Volts (L-L & L-N), frequency (Hz)
Coolant temperature
1 Programmable digital outputs
Speed adjust
Engine cycle crank
Over/under voltage (27/59)
kW-hr (total)
6 Customer programmable digital inputs
Generator phase sequence
1 Programmable relay outputs (Form C)
PLC functionality
kVAr-hr (total)
DC volts
Engine cool-down timer
24 Volt DC operation
Generator mounted - rear facing
High coolant temperature
Amps (per phase & average)
Load histogram feature
Emergency stop pushbutton
Warning/shutdown with common LED indication of shutdowns for:
kVAr (per phase, average & percent)
Customizable screens
True RMS AC metering, 3-phase, +/-2% accuracy
Overcurrent (50/51)
Communications:
kVA (per phase, average & percent)
Power factor (per phase & average)
Failure to start (overcrank)
Accessory module data link
Lamp test
Generator set packages include Caterpillars voltage regulator
Exhaust
Exhaust flange outlet
Fuel
Primary fuel filter with integral water separator
Generator
IP23 Protection
Power Termination
Busbar
Control Panel
Cat ECS Genset controller
Cooling System
Package mounted radiator
Exhaust System
Dry exhaust manifold
Flanged faced outlet(s)
Fuel System
Fuel priming pump
Fuel cooler; not included with packages without radiator
Flexible fuel lines - shipped loose
Secondary fuel filters
General
SAE standard rotation
Paint - Caterpillar yellow except rails and radiators gloss black
RH service
Flywheel and Flywheel housing-SAE No. 00
Generators and Attachments
Matched to the performance and output characteristics of Cat engines
Random wound
Busbar connections, right side extension box, bottom cable entry - 60 Hz models: NEMA standard hole pattern
Permanent magnet excitation (PMG)
LV
HV:
MV:
6 Lead
Winding temperature detectors
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby) - 60 Hz models: NEMA standard hole pattern
Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)
3 Phase brushless, Salient pole
Anti-condensation space heater
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)
Form wound
Governing System
ADEM A3
Lube System
Gear type lube oil pump
Oil filter, filler and dipstick
Oil drain lines and valve
Integral lube Oil cooler
Lubricating oil
Fumes disposal
Mounting System
Rails - Engine/generator/radiator mounting
Rubber anti-vibration mounts - shipped loose
Anti-vibration mounts (shipped loose)
Starting System
45 Amp Charging alternator
24 Volt electric starting motor
Battery disconnect switch
Battery and battery rack w/cables
Optional Equipment
Exhaust
Exhaust mufflers <!--(except Tier 4)-->
Air Inlet System
Dual element air cleaner
Standard ambient radiators
Single element filter
Standard ambient ATAAC radiators
Optional radiator arrangements
Generator
Permanent magnet excitation (PMG)
Oversize and premium generators
Internal excitation (IE)
Anti-condensation heater
Control Panels
Load share module
Empty upper box
Generator main terminal box
Annunciator - remote
EMCP 4.4
Digital I/O module
Cable Shroud
Remote monitoring software
Vandal proof panel cover
Side extension box
Generator temperature monitoring & protection
Annunciator - local
Cooling System
Water level switch gauges
Coolant
Mounting
IBC isolators
Spring type vibration isolators
Crankcase Systems
No explosion relief valves
Explosion relief valves
Crankcase ventilation systems
Crankcase protection groups:
Exhaust System
Tier 4 dosing cabinet
Y Adapters
Flanges
Flange and exhaust expanders
Elbows>
Mufflers
Tier 4 lean emissions moDual
Clean emission parts
Flexible fittings
Tier 4 clean emission MOD kits
Exhaust offset
Starting/Charging
Charging alternator
Battery chargers
Oversize batteries
Heavy duty starting system
Jacket water heater
Air starting motor with control and silencer
Extended Service Coverage
Platinum, Silver and Gold coverage
General
The following options are based on regional and product configuration:
UL 2200 package
EEC Declaration of Conformity
CSA Certification
Enclosures: Sound attenuated, weather protective
EU Certificate of Conformance (CE)
Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
Integral & sub-base UL listed dual wall fuel tanks
Automatic transfer switches (ATS)
Integral & sub-base fuel tanks
Fuel System
Gas fuel filter
Primary fuel filter
Fuel priming pumps (Tier 4)
Generators and Attachments
1600 Frame - 380, 400, 415 Volts, 3 Phase 1500 rpm ,FW, PM, No. of leads = 6, Pitch = .6667
Hi voltage optional attachments
Differential current transformers
1600 Frame - 380, 400, 415 Volts, 3 Phase 1500 rpm, RW, PM, No. of leads = 6, Pitch = .6667
Generators high voltage
Space heater kit
Generator conversions
1600 Frame - 380, 400, 415 Volts, 3 Phase 1500 rpm, RW, IE, No. of leads = 6, Pitch = .6667
2700 Frame - 6300, 6600, 6900 Volts, 3 Phase 1500 rpm, FW, PM, No. of leads = 6, Pitch = .6667
3000 Frame - 10000, 10500, 11000 Volts, 3 Phase 1500 rpm, FW, PM, No. of leads = 6, Pitch = .6667
1800 Frame
Alternator air cleaner
Instrumentation
Pyrometer and termocouples
Lube System
Prelube pump groups
Oil level regulator
Lube oil in standard sump
Mounting System
IBC vibration isolators
Puck style low efficiency isolators
Spring type vibration isolators
Power Connections
Cable entry - right side
Cable entry - rear
Grounding groups
left side power connections
Neutral ground connections
Center post busbars
Right side power connections
Cable entry - left side
Rear power connections
Power Termination
Circuit breakers - LV packages
Circuit breakers, UL listed
2000, 2500, 3200 Amp, 3 Pole, IEC rated Circuit breakers
Circuit breakers, IEC compliant
2000, 2500, 3200 Amp, 4 Pole, IEC rated Circuit breakers
1600, 2000, 2500, 3000 and 4000 Amp, 3 Pole, UL-100% rated Circuit breakers
Special Tests / Reports
Standard engine test
Torsional vibration analysis
Fuel consumption test
PGS Test report @ 1.0 power factor
OSPD Certification
PGS Test report @ 0.8 power factor
Generator set report
Starting / Charging
Engine barring device
Electric starting motors
Jacket water heaters
Starter cover
Batteries, racks and cables
Air pressure regulator
10, 20, 35 Amp Battery chargers
50 Amp NFPA battery charger
Air starting motors